Metallic pipelines transporting hydrocarbons, water, and other industrial fluids can be exposed to electrical conditions capable of generating dangerous potential differences for operation and maintenance personnel. Proximity to overhead electrical transmission lines, insulation faults, lightning discharges, and electromagnetic induction phenomena constitute sources of risk that must be considered during the design and operation of these facilities.
In certain scenarios, a person may be exposed to a potential difference between their feet or between a metallic structure they touch and the ground on which they stand. These phenomena are known as step and contact potentials, respectively, and can produce electrical currents through the human body with severe consequences.
Gradient Control Mats (GCM) constitute an engineering solution aimed at limiting these potential differences around exposed access points, valves, test stations, and other pipeline components.
However, their integration requires considering an additional aspect: compatibility with cathodic protection systems. In this context, GCM mats from Dairyland Electrical Industries, combined with Solid-State Decouplers (SSD), offer an alternative to simultaneously address personnel safety and the continuity of anticorrosion protection.
Step and contact potentials around pipelines
Dangerous potentials originate when an electrical current flows through the ground or raises the potential of a metallic structure relative to earth. In pipelines close to electrical installations, these phenomena can occur during normal operating conditions, electrical faults, or lightning discharges.
Electromagnetic induction can produce alternating current (AC) voltages in pipelines that share corridors with transmission lines. On the other hand, a phase-to-ground fault can transfer currents into the ground and generate significant step and ground potential rises. Lightning discharges can also introduce high-amplitude, high-frequency transients.
From an electrical safety standpoint, it is necessary to distinguish two conditions:
- Step voltage: potential difference between two points on the ground surface separated by the distance corresponding to a person’s foot position. Current can flow from one leg to the other.
- Touch voltage: potential difference between an accessible metallic structure and the point on the ground where the person stands. It can establish a current path between hand and feet.
In pipeline facilities, these conditions can occur around above-ground piping, valves, metering stations, junction boxes, and cathodic protection test points.
The magnitude of the risk depends on the applied voltage, the current path, the duration of exposure, soil conditions, and the electrical characteristics of the grounding system.
Therefore, evaluation should not be limited to measuring AC voltage on the pipeline. It is necessary to determine step and touch voltages under representative operating and fault scenarios, considering site-specific conditions.
GCM gradient control mats to reduce personnel exposure
Gradient control mats are conductive systems installed in the ground around accessible metallic components. Their function is to modify the spatial distribution of electrical potential, reducing voltage differences that may appear between nearby points on the surface.
Unlike configurations consisting of a single conductor arranged in a spiral or zigzag pattern, a grid mat provides multiple conductive paths and reduced distances between its connection points. This geometry contributes to reducing local potential differences, particularly during fast transients.
Configuration and operating principle
Dairyland Electrical Industries develops robust electronic technologies that ensure electrical safety, reliability, and anticorrosion protection in critical infrastructure. A pioneer in solid-state decouplers and surge protectors, the company has established itself as a benchmark in oil and gas, energy, transportation, and maritime sectors.
The GCM solution from Dairyland Electrical Industries offers safe technical solutions, installation, and application in pipeline facilities. It utilizes a configuration of galvanized steel conductors arranged in a grid of approximately 3 × 3 inches, with welded intersections. Its low-inductance design seeks to limit voltage differences associated with AC faults and lightning discharges.
The mat is installed in areas where personnel can come into contact with energized metallic components, generally under a surface layer of high-resistivity material, such as washed gravel, in accordance with the site design.
Its performance depends on variables such as:
- Mat geometry and dimensions.
- Length and configuration of connection conductors.
- Soil resistivity and stratification.
- Characteristics of the fault current or transient.
- Installation conditions and electrical continuity.
- Location of points accessible to personnel.
A particularly important aspect is that lightning events cannot be analyzed as simple industrial-frequency AC phenomena. Their high-frequency content causes conductor inductance and connection length to have a significant influence on developed voltage differences.
For this reason, a mat that is suitable for 50 or 60 Hz induction conditions does not necessarily provide the same behavior against a lightning discharge.
Configuration selection must be supported by an engineering evaluation that considers applicable electrical scenarios and corresponding safety criteria.
Decoupling of the GCM with SSD without compromising cathodic protection
Integrating a conductive mat with a cathodically protected pipeline introduces a relevant electrochemical consideration: the electrical interaction between both systems.
When a metallic mat is directly connected to a pipe, a direct current (DC) exchange path can be established. Depending on the materials, soil conditions, and system configuration, this connection can alter cathodic protection current distribution, affect potential measurements, and generate additional current demands.
The problem becomes significant when the mat incorporates materials with electrochemical behavior different from that of the pipeline or when stray current paths exist.
Function of the SSD device
The Solid-State Decoupler (SSD) device is installed between the GCM mat and the protected structure to provide an electrical connection with different behavior depending on the type of signal applied.
Functionally, it allows to:
- Block the flow of direct current associated with cathodic protection under its operating conditions.
- Provide electrical continuity for alternating current and transient conditions within its rated characteristics.
- Reduce interaction between the mat and the cathodic protection system.
- Facilitate obtaining cathodic protection potential measurements in the vicinity of the mat.
- Avoid unnecessary protection current demands associated with direct connection.
Dairyland recommends decoupling its GCM mats using SSDs to reduce interaction with cathodic protection and allow measurements near the installation.
Device selection must consider available fault current, the magnitude and duration of transients, voltage levels, and installation conditions. Likewise, connection lengths must be kept short due to their influence on the response to high-frequency impulses.
It is important to clarify that the SSD does not replace cathodic protection design or AC mitigation evaluation. Its function is to provide DC decoupling and electrical continuity under the conditions for which it has been specified.
NACE SP0177-2026 and safety against AC and lightning effects
The NACE SP0177-2026 standard, Mitigation of Alternating Current and Lightning Effects on Metallic Structures and Corrosion Control Systems, establishes recognized practices for mitigating the effects of alternating current and lightning discharges on metallic structures and corrosion control systems.
This edition replaces NACE SP0177-2019 and includes measures applicable during the design, construction, operation, and maintenance of facilities.
In the context of pipelines, its application must be approached from two complementary perspectives:
- Electrical safety: evaluation and mitigation of step and touch voltages that may occur during normal conditions, electrical faults, and transient events.
- Corrosion control: consideration of electrical effects on metallic structures and cathodic protection systems, preventing safety measures from introducing detrimental interactions.
The engineering evaluation must consider actual site conditions, proximity to power lines, soil resistivity, personnel access points, and voltage source characteristics.
Installing a GCM mat should not be interpreted as an automatic guarantee of safety. Its effectiveness depends on design, proper connection, ground conditions, and verification of step and touch potentials for the scenarios considered.
Conclusions
Step and touch potentials represent a relevant electrical risk in pipelines exposed to AC induction, electrical faults, and lightning discharges. Their mitigation requires an engineering approach that considers both operating conditions and the most severe transient events.
GCM gradient control mats constitute a solution for reducing potential differences around components accessible to personnel. Their grid and low-inductance configuration makes it possible to address conditions that can be difficult to control using single-conductor systems.
Integration with cathodically protected pipelines must account for the interaction between the grounding grid and the anti-corrosion system. Decoupling via SSD devices limits direct current exchange while maintaining an electrical path for the alternating current and transient conditions specified in its requirements.
Personnel safety and the electrochemical integrity of the pipeline should not be addressed as independent objectives. The selection and configuration of GCM grids, along with properly specified decoupling, allow both aspects to be addressed within a coordinated technical solution.
The application of NACE SP0177-2026 reinforces the need to integrate electrical safety, AC and lightning effect mitigation, and corrosion control within a single engineering strategy.
References
- Dairyland Electrical Industries. (n.d.). GCM: Gradient Control Mat. https://www.dairyland.com/product/gcm/
- Dairyland Electrical Industries. (n.d.). Gradient control mat decoupling. https://www.dairyland.com/applications/gradient-control-mat-decoupling/
- Dairyland Electrical Industries. (n.d.). Don’t take chances with grounding mat design—Protect your workers! https://www.dairyland.com/knowledge-base/dont-leave-grounding-mat-design-to-chance-protect-your-workers/
- Dairyland Electrical Industries. (2021). Gradient control mat: Technical literature (Document ID 200002). https://www.dairyland.com/wp-content/uploads/2021/02/GCM_Literature_200002.pdf
- NACE International. (2026). NACE SP0177-2026: Mitigation of alternating current and lightning effects on metallic structures and corrosion control systems. AMPP.